SuperSumpFlush
The SuperSumpFlush is a fully automatic waste water pumping system suitable for pumping storm water to a higher level when gravity drainage is not possible or economical to install.
The system is suitable for installing either at the initial building stage or retro fitting to existing buildings and can accept waste from car parks, car washes, floor areas, down pipes or similar.
The system consists of a polyethylene tank with a built in automatic waste water submersible pump. It can accept storm water through the grille located on the top of the unit or through two 110mm inlets located to the side (side inlets to be specified at time of order).
Dimensions
|
Model
|
Diameter
|
Height
|
|
SuperSumpFlush
|
500mm
|
600mm
|
Specification
|
Model
|
SuperSumpFlush
|
|
Power Supply
|
230V AC
|
|
Rated Current
|
3.4A
|
|
Motor Rating
|
700W
|
|
Frequency
|
50Hz
|
|
Revolutions per Minute
|
2800rpm
|
|
Max. Vertical Output
|
12m
|
|
Max. Horizontal Output
|
100m
|
|
Max. Flow Rate
|
240 l/m
|
|
Max. Liquid Temp.
|
<40°C
|
|
Discharge Size
|
32mm
|
|
Cable Length
|
3m
|
|
Weight
|
15kg
|
|
Colour
|
White
|
Installation guidelines
It is important to note that these instructions are for guidance only. Please refer to the full Installation and Operating Guidelines when specifying / installing the product.
Siting the product
The SuperSumpFlush is designed for installation below ground so the ground conditions should be taken into account prior to locating the unit. Wherever possible roadway installations should be avoided, however if this is not possible any imposed loads should be also taken into account.
It is extremely important to site the SuperSumpFlush with access in mind in the event of maintenance being required.
Inlet connections
The SuperSumpFlush comes as standard complete with a heavy-duty polypropylene grille which acts as the inlet for surface water. If a rainwater downpipe or gully is to drain into the unit then a 110mm rubber connector is located on the side of the tank to accept 110mm uPVC waste pipe. The 110mm waste pipe should be pushed into the rubber connector to form a watertight seal around the incoming waste pipe.
Discharge connection
The discharge line must be connected to the SuperSumpFlush via the tank connector on the side of the unit. The tank connector will accept 32mm uPVC waste pipe. All joins in the discharge line must be made with solvent cement, under no circumstances should push fit or compression fittings be used.
The SuperSumpFlush is designed to pump upwards on a gradient or for one vertical lift only; this vertical lift must be made within 500mm of the unit.
IMPORTANT – It is recommended that there are no bends in the vertical lift, however if this is unavoidable a minimum of slow radius bends may be used.
Electrical connection
A qualified person in accordance with the Institute Of Electrical Engineers Regulations should connect the unit to the appropriate mains supply taking into account all the electrical information provided.
IMPORTANT – All pump systems must be used with an appropriate motor rated protection device.
Maintenance
The SuperSumpFlush requires minimal maintenance. Basic common sense and good housekeeping will ensure the best results. It is recommended that the unit be inspected visually at least once a month by lifting the grille, with any debris (i.e. leaves, twigs, stones etc.) being removed. At least every six months it is advised to check the operation of the float switch and also clean the tank with a minimum of bleach or other domestic cleaning products.
Health & safety
As with all site work, the danger of working with water and electricity can pose a severe threat to health if obvious and fundamental precautions are not taken. Therefore if you are in any doubt regarding the installation, please contact us.
All site work must be undertaken by qualified personnel only.
These notes are for guidance only and it is for the installer to ensure the installation is in accordance with all structural and regulatory requirements.
Our policy is one of continuous product improvement, we reserve the right to change specifications and prices without prior notice. All information is given in good faith.
|
|
|||||||
|
|